Electrical Load Calculator
Optional. Used to check available panel capacity.
| Equipment / Load Description | Load Type | Watts Each | Qty | Total Watts |
|---|
Load Calculation Results
Optional. Leave blank to see available capacity only. Use our Watts to Amps Calculator to convert wattage to amps.
Panel Capacity Results
What This Electrical Load Calculator Does
This free tool helps facility managers, property owners, and electrical contractors estimate circuit and panel loads for commercial buildings. Unlike residential load calculators that focus on home appliances and service entrance sizing, this calculator is built around the real commercial use cases FSG's team handles every day: adding EV chargers to a warehouse, retrofitting LED lighting across a large facility, installing new HVAC equipment in a tenant space, or checking whether an existing panel has room for new loads before calling an electrician.
Mode 1 (Add-a-Load Checker) lets you build a list of equipment, calculates total amps drawn, and applies the NEC 80% continuous load rule to recommend a minimum breaker size and wire gauge. Mode 2 (Panel Capacity Checker) lets you enter your existing panel size and estimated current load to see how much capacity you have left before a panel upgrade becomes necessary.
For the underlying amp conversion math, see our Watts to Amps Calculator. For EV charger installation at your facility, see FSG's commercial EV charging services.
The Formulas This Calculator Uses
Single Phase Load
Three Phase Load
NEC 80% Rule
Common Commercial Equipment Load Reference
Use these typical wattage values when building your load list. Actual values vary by manufacturer and model. Always verify against the equipment nameplate for permitted work.
| Equipment Type | Typical Wattage | Voltage / Phase | Load Type | Notes |
|---|---|---|---|---|
| LED Troffer (2x4) | 40-50W | 120V or 277V, 1ph | Continuous | Most common commercial office fixture |
| LED High Bay (100W) | 100W | 120/277V, 1ph | Continuous | Warehouse and industrial ceiling lights |
| LED High Bay (200W) | 200W | 277/480V, 1ph | Continuous | High-ceiling distribution centers |
| Rooftop HVAC (5 ton) | 5,000-6,000W | 208/240V, 3ph | Continuous | Typical small commercial unit |
| Rooftop HVAC (10 ton) | 10,000-12,000W | 208/480V, 3ph | Continuous | Mid-size commercial unit |
| EV Charger Level 2 (EVSE) | 7,200W (30A) | 208/240V, 1ph | Continuous | NEC requires 125% sizing for EVSE |
| EV Fast Charger (DC) | 50,000W+ | 480V, 3ph | Continuous | Requires load study for most facilities |
| Air Compressor (5 HP) | 3,730W | 208/240V, 3ph | Non-continuous | Motor load, typically cyclic |
| Air Compressor (10 HP) | 7,460W | 208/480V, 3ph | Non-continuous | Motor load, typically cyclic |
| Commercial Refrigeration | 1,500-3,000W | 208/240V, 1ph | Non-continuous | Cycles on and off |
| Office Workstation (avg) | 300-400W | 120V, 1ph | Non-continuous | Per NEC 220.14, use 180VA minimum per receptacle |
| Server / IT Rack | 3,000-10,000W | 208V, 1ph or 3ph | Continuous | Verify nameplate; treat as continuous |
Commercial Electrical Load Calculation Example
A worked example: a facility manager at a 50,000 sq ft distribution center wants to add 8 Level 2 EV chargers (7,200W each) on a 208V three-phase panel currently rated at 400A and estimated 60% loaded.
Step 1 — Total New Load Wattage
- 8 chargers x 7,200W = 57,600W total
- EV chargers are continuous loads (NEC 625.42)
Step 2 — Convert to Amps (Three Phase)
- Amps = 57,600 / (208 x 1.732) = 57,600 / 360.3 = 159.9A
- NEC 80% continuous load rule: 159.9 / 0.8 = 199.9A minimum breaker
- Next standard size: 200A breaker required
Step 3 — Check Panel Capacity
- 400A panel at 60% loaded = 240A already in use
- Available: 400A - 240A = 160A remaining
- New load requires 200A. Panel is 40A short.
- Verdict: Panel upgrade required before installation
Standard Commercial Panel Sizes and Ampacity
| Panel Size | NEC 80% Continuous Limit | Typical Application | Common Voltage |
|---|---|---|---|
| 100A | 80A continuous | Small tenant suites, single-zone retail | 120/240V 1ph |
| 200A | 160A continuous | Mid-size offices, restaurants, small retail | 120/208V 3ph |
| 400A | 320A continuous | Large offices, warehouses, distribution | 120/208V or 277/480V 3ph |
| 600A | 480A continuous | Large retail, multi-tenant commercial | 277/480V 3ph |
| 800A | 640A continuous | Industrial facilities, data centers | 277/480V 3ph |
| 1,200A | 960A continuous | Large manufacturing, campus feeders | 277/480V 3ph |